JBJ SP6 56-62 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Iveco |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 56/44.8 |
STP generator power (kVA)/KWe | 62/49.6 |
Cos Phi power factor | 0.8 |
Number of cylinders | 4 in line |
Speed (R.P.M.) | 1.800 |
Fuel consumption (l/h) | At 100%: 14.4 l/h |
At 75%: 10.8 l/h | |
Open generator fuel tank | 91 l |
Soundproofed generator fuel tank | 150 l |
Max. exhaust gas temperature 100% (ºC) | 502 |
Exhaust gas flow 100% (m3/min) | 291 |
Max. acceptable backpressure (Kpa) | 5 |
Air required for combustion 100% (m3/h) | 215 |
Alternator fan air flow (m3/m) | 14.5 |
Motor fan air flow (m3/s) | 7200 |
Open generator weight | 750 Kg |
Soundproofed generator weight | 1300 Kg |
Open
- H: 1400 mm
- L: 1900 mm
- W: 700 mm
Closed
- H: 1800 mm
- L: 2600 mm
- W: 1100 mm
JBJ MP6 112-125 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Iveco |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 112/89,6 |
STP generator power (kVA)/KWe | 125/100 |
Cos Phi power factor | 0.8 |
Number of cylinders | 4 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 25 l/h |
At 75%: 17.82 l/h | |
Open generator fuel tank | 200 l |
Soundproofed generator fuel tank | 200 l |
Max. exhaust gas temperature 100% (ºC) | 588 |
Exhaust gas flow 100% (m3/min) | 634 |
Max. acceptable backpressure (Kpa) | 5 |
Air required for combustion 100% (m3/h) | 678 |
Alternator fan air flow (m3/m) | 21.3 |
Motor fan air flow (m3/s) | 9360 |
Open generator weight | 1250 Kg |
Soundproofed generator weight | 1950 Kg |
Open
- H: 1600 mm
- L: 2350 mm
- W: 750 mm
Closed
- H: 1800 mm
- L: 2900 mm
- W: 1100 mm
JBJ MP6 140-150 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Iveco |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 140/112 |
STP generator power (kVA)/KWe | 155/124 |
Cos Phi power factor | 0.8 |
Number of cylinders | 6 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 31.8 l/h |
At 75%: 25.5 l/h | |
Open generator fuel tank | 200 l |
Soundproofed generator fuel tank | 350 l |
Max. exhaust gas temperature 100% (ºC) | 580 |
Exhaust gas flow 100% (m3/min) | 757 |
Max. acceptable backpressure (Kpa) | 5 |
Air required for combustion 100% (m3/h) | 522 |
Alternator fan air flow (m3/m) | 21.23 |
Motor fan air flow (m3/s) | 14400 |
Open generator weight | 1425 Kg |
Soundproofed generator weight | 2275 Kg |
Open
- H: 1500 mm
- L: 2200 mm
- W: 700 mm
Closed
- H: 1950 mm
- L: 3400 mm
- W: 1350 mm
JBJ MP6 200-220 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Iveco |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 200/160 |
STP generator power (kVA)/KWe | 220/176 |
Cos Phi power factor | 0.8 |
Number of cylinders | 6 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 44 l/h |
At 75%: 35.7 l/h | |
Open generator fuel tank | 200 l |
Soundproofed generator fuel tank | 350 l |
Max. exhaust gas temperature 100% (ºC) | 550 |
Exhaust gas flow 100% (m3/min) | 786 |
Max. acceptable backpressure (Kpa) | 6 |
Air required for combustion 100% (m3/h) | 754 |
Alternator fan air flow (m3/m) | 32 |
Motor fan air flow (m3/s) | 3.8 |
Open generator weight | 1750 Kg |
Soundproofed generator weight | 2650 Kg |
Open
- H: 1700 mm
- L: 2750 mm
- W: 800 mm
Closed
- H: 2150 mm
- L: 3800 mm
- W: 1350 mm
JBJ MP6 228-250 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Iveco |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 235/188 |
STP generator power (kVA)/KWe | 250/200 |
Cos Phi power factor | 0.8 |
Number of cylinders | 6 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 69.7 l/h |
At 75%: 52.4 l/h | |
Open generator fuel tank | 300 l |
Soundproofed generator fuel tank | 350 l |
Max. exhaust gas temperature 100% (ºC) | 636 |
Exhaust gas flow 100% (m3/min) | 1280 |
Max. acceptable backpressure (Kpa) | 6 |
Air required for combustion 100% (m3/h) | 1180 |
Alternator fan air flow (m3/m) | 38 |
Motor fan air flow (m3/s) | 1800 |
Open generator weight | 2500 Kg |
Soundproofed generator weight | 3400 Kg |
Open
- H: 1700 mm
- L: 2800 mm
- W: 800 mm
Closed
- H: 1950 mm
- L: 3400 mm
- W: 1350 mm
JBJ MP6 350-390 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Doosan |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 300/240 |
STP generator power (kVA)/KWe | 330/264 |
Cos Phi power factor | 0.8 |
Number of cylinders | 6 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 63 l/h |
At 75%: 47 l/h | |
Open generator fuel tank | 300 l |
Soundproofed generator fuel tank | 350 l |
Max. exhaust gas temperature 100% (ºC) | 590 |
Exhaust gas flow 100% (m3/min) | 1442 |
Max. acceptable backpressure (Kpa) | 6 |
Air required for combustion 100% (m3/h) | 1298 |
Alternator fan air flow (m3/m) | 32 |
Motor fan air flow (m3/s) | 5.67 |
Open generator weight | 2560 Kg |
Soundproofed generator weight | 3510 Kg |
Open
- H: 1700 mm
- L: 3300 mm
- W: 1150 mm
Closed
- H: 2200 mm
- L: 4500 mm
- W: 1700 mm
JBJ MP6 375-414 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Iveco |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 350/280 |
STP generator power (kVA)/KWe | 385/308 |
Cos Phi power factor | 0.8 |
Number of cylinders | 6 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 70 l/h |
At 75%: 57.3 l/h | |
Open generator fuel tank | 300 l |
Soundproofed generator fuel tank | 350 l |
Max. exhaust gas temperature 100% (ºC) | 479 |
Exhaust gas flow 100% (m3/min) | 1549 |
Max. acceptable backpressure (Kpa) | 5 |
Air required for combustion 100% (m3/h) | 1495 |
Alternator fan air flow (m3/m) | 32 |
Motor fan air flow (m3/s) | 6.8 |
Open generator weight | 3100 Kg |
Soundproofed generator weight | 4300 Kg |
Open
- H: 1750 mm
- L: 3450 mm
- W: 1300 mm
Closed
- H: 2200 mm
- L: 4500 mm
- W: 1700 mm
JBJ MP6 450-500 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | Iveco |
Cooling systems | Radiator |
PRP generator power (kVA)/KWe | 400/320 |
STP generator power (kVA)/KWe | 440/352 |
Cos Phi power factor | 0.8 |
Number of cylinders | 6 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 87.5 l/h |
At 75%: 72.5 l/h | |
Open generator fuel tank | 300 l |
Soundproofed generator fuel tank | 350 l |
Max. exhaust gas temperature 100% (ºC) | 445 |
Exhaust gas flow 100% (m3/min) | 1836 |
Max. acceptable backpressure (Kpa) | 5 |
Air required for combustion 100% (m3/h) | 1770 |
Alternator fan air flow (m3/m) | 54 |
Motor fan air flow (m3/s) | 6.8 |
Open generator weight | 3200 Kg |
Soundproofed generator weight | 4400 Kg |
Open
- H: 1750 mm
- L: 3450 mm
- W: 1300 mm
Closed
- H: 2200 mm
- L: 4500 mm
- W: 1700 mm
JBJ XLP6 500-550 KVA
60 Hz - 1800 rpm | Voltage: 480 / 277 V |
---|---|
Motor model | SCANIA |
Cooling systems | Radiador |
PRP generator power (kVA)/KWe | 450/360 |
STP generator power (kVA)/KWe | 500/400 |
Cos Phi power factor | 0.8 |
Number of cylinders | 6 in line |
Speed (R.P.M.) | 1800 |
Fuel consumption (l/h) | At 100%: 91.42 l/h |
At 75%: 68.54 l/h | |
Open generator fuel tank | 300 l |
Soundproofed generator fuel tank | 450 l |
Max. exhaust gas temperature 100% (ºC) | 536 |
Exhaust gas flow 100% (m3/min) | 1975 |
Max. acceptable backpressure (Kpa) | 16 |
Air required for combustion 100% (m3/h) | 1600 |
Alternator fan air flow (m3/m) | 1.035 |
Motor fan air flow (m3/s) | 9.58 |
Open generator weight | 2917 Kg |
Soundproofed generator weight | 5190 Kg |
Open
- H: 1750 mm
- L: 3650 mm
- W: 1250 mm
Closed
- H: 2200 mm
- L: 4500 mm
- W: 1700 mm